Line 33: Line 33:
 
Prior to Revision ** (prior to 135-2006) Max APDU was 480 bytes.  
 
Prior to Revision ** (prior to 135-2006) Max APDU was 480 bytes.  
  
NPCImax = 9 + 6 byte MAC + 7 byte MAC = 22
+
[[NPCI]]max = 9 + 6 byte MAC + 7 byte MAC = 22
  
 
So [[NSDU]]max = 480 + 22 = 502
 
So [[NSDU]]max = 480 + 22 = 502

Revision as of 23:21, 11 November 2018

BACnet "Master-Slave/Token-Passing" is the optional, RS-485 based physical layer for BACnet. It is based on cheap, relatively slow, serial communications.


Starting with Addendum 135-2008ab, 9600 and 38400 are the required baud rates and all of the others (19200, 57600, 76800, and 115200) are optional


MS/TP Frame Format
0x55 Framing 1
0xFF Framing 2
Frame Type
Dest MAC
Src MAC
Len MSByte
Len LSByte
Header CRC
Data if len non-zero
Data CRC MSByte if len non-zero
Data CRC LSByte if len non-zero


Prior to Revision ** (prior to 135-2006) Max APDU was 480 bytes.

NPCImax = 9 + 6 byte MAC + 7 byte MAC = 22

So NSDUmax = 480 + 22 = 502

And NSDUmax + 10 (above) = 512